Dead End Insulators

DEAD END INSULATORS

SUSPENSIONS & DEAD END INSULATORS

TECHNICAL DATA

  Catalogue No.  DPL11-560  DPL20-815  DPL33-1080  DPL33-1330
  Rated Voltage KV  13.8  24  36  36
  Shed No.  4  6  8  10
Specified Mechanical Load(SML) KN 70  70  70  70
Section Length H.mm 393 465 537 609
Shed Diameter D.mm 124 124 124 124
Space Between Two Sheds B.mm 36 36 36 36
Creapage Distance mm 560 815 1080 1330
Dry Arcing Distance h.mm 298 370 440 510
Lightning Impuls
Withstand Voltage KV
Positive 180 240 260 290
Negative 205 255 290 380
60 Hz Flashover
Withstand Voltage KV
Dry 110 135 150 175
Wet 58 110 125 150
Standard Package 12 12 12 9